What the Electrical Drawing Needs for a Fragrance Diffuser

SOSA · The Founder Diaries · For Interior Designers

A point in the wrong place cannot be moved.

The socket wants to be at 90 cm to 120 cm above finished floor — about two feet eleven to three feet eleven — a band topping out at the switch-plate datum your drawing already uses, not the skirting datum 600 mm below its foot. At drawing stage that line costs nothing; after plaster it costs a wall.

I have stood in a finished drawing room beside a client, looking at a 5-amp point at skirting level behind a sofa back, the stone already up and no honest way to use it. The only thing left to specify in that room was a bottle.

SOSA Pawan waterless diffuser plugged straight into the wall, with nothing standing on a surface
SOSA Pawan, ₹6,999 — a plug-in waterless unit for one closed room, quoted to 500 sq ft; it needs one point and nothing else on the drawing.

Send us the layout — SOSA on WhatsApp →

The answer in 30 seconds

What the Electrical Drawing Needs for a Fragrance Diffuser

  • In one line. One switched 5-amp point per scented volume, at 90 cm to 120 cm above finished floor, in the half of the room people use — marked before plaster, because afterwards it is a wall you do not open.
  • Height is the whole argument. 90 cm to 120 cm is about 2 ft 11 in to 3 ft 11 in. The electrician will offer the general datum at 300 mm; the 600 to 900 mm between it and the band is the difference between releasing below a sofa seat and releasing where a seated person breathes.
  • Position in plan is a list of things to avoid. Not under a ceiling fan — for a 1,200 mm sweep, stay about 1.2 m clear of its centre, twice the blade-tip radius. Not within about 1.5 m of a return-air grille. Not in a supply diffuser's throw. Not beside a door or window the family keeps open.
  • Switched at a plate, never on the lighting scene. The client should be able to kill the point without pulling the plug — but the device holds its own schedule over Bluetooth, so a scene or a master off hands the housekeeper a switch that silently cancels it.
  • Neither machine needs a dedicated circuit. The load is small enough that a standard point on the room's existing circuit is sufficient; the figures are on the product page.₹6,999 · ₹12,499
  • If you only do one thing: write the point and its height into the mark-up back to the electrical consultant, in the same revision as the FF&E line. A diffuser nobody drew is one the client buys and cannot site anywhere.

Ask SOSA before the electrical drawing is issued →

The answer, in full

Fragrance arrives late. It goes on the FF&E schedule after the furniture and the lighting, often after the client has asked for it in a meeting — and by then the electrical layout is issued, the conduits are in the wall and the chases plastered over. Nothing else on that sheet behaves this way: a chair in the wrong place is moved, a wrong lamp is swapped, and a 5-amp point in the wrong place is a hole in finished plaster — on a stone-clad wall, not even that, but a wall you do not open. So the one stage at which room fragrance is cheap to specify is the stage at which nobody is thinking about it. What the drawing needs is very little. One point, at 90 cm to 120 cm above finished floor — roughly two feet eleven to three feet eleven — a band whose top is the datum your switch plates are already drawn at. The socket an electrician will offer sits at skirting level, usually 300 mm, so the band starts 600 mm above it and ends at the switch-plate datum at 1,200 mm — the difference between releasing below the seat of a sofa and releasing where a seated person breathes; general ventilation design guidance typically puts the seated breathing zone a little above a metre and the standing one near 1.7, so the band I want brackets the seated level rather than the standing one, which is not an accident. The second thing it needs is a position in plan, and that instruction is mostly negative. Not under a ceiling fan: for the common 1,200 mm sweep the blades describe a circle of 0.6 m radius, and the same again puts the point about 1.2 m clear of its centre, because a fan does not distribute fragrance, it shreds it. Not beside a return-air grille, whose pull falls away roughly with the square of the distance, so three face widths off — about 1.5 m from a 500 mm grille — leaves near a ninth of the face velocity and a point no longer in argument with the air handling. Not in the throw of a supply diffuser. Not within reach of an external door or a window the family keeps open all year. And not, the one I see most often, on the wall that will later carry the television, the mirror, the art or the joinery, because a point behind a fixed object cannot be used. The third thing is a plate switch, with a note that the point is not to join the lighting scene. A portion of every SOSA order supports girl-child education through Nanhi Kali, and it is the only line in this specification that needs no socket.

Specifying a point you will not have to move

Put it at plate height, not at the skirting

Draw it at 90 cm to 120 cm above finished floor and dimension it, because an undimensioned dot becomes a 300 mm socket by default. That 600 to 900 mm is the whole specification: a unit at skirting level behind furniture scents the underside of a sofa, and one on a high ledge scents air nobody stands in. If the room is tall, convert the room to cubic metres first, then come back here — the height of the point does not change with the height of the room.

Choose the wall against the joinery drawing, not the plan

Lay the electrical layout over the elevations and the furniture plan before you commit. The wall you want is in the used half of the room, clear of the television, the mirror, the art wall and fitted joinery, and its finish must take a plate — not the one panelled in veneer at the last revision.

Draw the clearances, not just the dot

Mark the circles you are keeping clear, so the services consultant sees the intent. About 1.2 m from a 1,200 mm fan's centre, about 1.5 m from a return-air grille, about 2 m from a ceiling supply diffuser and out of its throw — design guidance typically puts a residential diffuser's throw at a couple of metres before it decays. In a 16 by 18 ft bedroom, 288 sq ft or 26.8 m², the fan exclusion is a circle of some 4.5 m² — about a sixth of the plan.

Switch it at a plate, and keep it off the scene

A plate switch beside the point, so the client can turn the device off without reaching behind a console — and then the sentence that matters more: this point joins no lighting scene, master off or room-off circuit. The machine keeps its own hours in the SOSA app, and a housekeeper who kills the lighting master at night cancels a schedule she does not know exists.

SOSA Vaayu waterless diffuser serving a tall reception space as one volume
SOSA Vaayu, ₹12,499 — quoted to 1,000 m³, supplied with 400 ml of fragrance, and wanting a point it keeps for years, not one borrowed from a console.

See the SOSA Vaayu specification →

The 5-amp point, and what it changes

On the drawing What to specify and why
Height One 5-amp point at 900 mm to 1,200 mm above finished floor — about 2 ft 11 in to 3 ft 11 in — dimensioned, not implied. Undimensioned it is built at the 300 mm datum, and the 600 to 900 mm lost is the difference between a device at seated breathing height and one behind a sofa back.
Position in plan In the used half of the room, off the main sightline from the door, never behind the seating group.
Wall selection Not the wall that will later carry the television, a mirror, the art hang or fitted joinery; and a finish that will take a plate. Check the elevations at the revision where cladding appears.
Clearances About 1.2 m clear of a 1,200 mm fan's centre — twice the blade-tip radius. About 1.5 m from a return-air grille: three face widths, roughly a ninth of the face velocity. About 2 m from a supply diffuser, out of its throw. Clear of an external door or a habitually open window.
Switching A plate switch adjacent, so the point can be killed without unplugging — and explicitly excluded from scene, master-off and room-off circuits, because the device carries its own schedule and a nightly master off cancels it silently.
Circuit No dedicated circuit. The load is small enough that a standard point on the room's existing circuit is sufficient; the figures belong on the product page.
Retrofit Plaster finished and no point: three honest answers and no fourth — a surface conduit the client is shown and accepts, a floor box if the floor is still open, or a 130 ml reed bottle at ₹1,499 to ₹1,599 and no electrical work.
The mark-up One line to the electrical consultant, in the same revision as the FF&E entry: point reference, room, height above finished floor, switched, excluded from scene control, clearances noted.

“Fragrance is a furniture decision with an electrical deadline, and the deadline is plaster.”

The sequence

  1. Put the fragrance line on the schedule early, while the electrical layout is still in revision rather than on site — it is the only line on the sheet with a construction deadline.
  2. Mark one point per scented volume, not one per room — a space with no door across it takes one point, however many names the plan gives it.
  3. Dimension the height at 90 cm to 120 cm above finished floor on the layout itself, so it cannot default to the 300 mm datum.
  4. Overlay the joinery and furniture drawings and move the point off any wall that will carry a television, a mirror, art or fitted units.
  5. Draw the clearance circles — fan, return grille, supply diffuser, open window — so services coordination picks them up rather than discovering them.
  6. Issue the mark-up with the switching note: plate switch adjacent, excluded from all scene and master-off control, with the FF&E line copied beside it.

SOSA · for interior designers

Two machines, one point each

SOSA Pawan nebulises undiluted oil into a dry mist — no water, no heat, nothing standing in a tray. It plugs into an ordinary 5-amp point, runs silently, and is set to hours and burst lengths over Bluetooth in the SOSA app, which is exactly why its point must not sit on a lighting scene. It arrives with 200 ml of oil as two 100 ml bottles in one of two fixed pairings, and a one-year warranty.

SOSA Vaayu is the same principle at floor scale, quoted to 1,000 cubic metres and supplied with 400 ml of fragrance. It is the unit for an open floor, a tall living room or a reception that reads as one volume — and because it stays put for years, its point is the one worth arguing about on the drawing.

SOSA Pawan ₹6,999 · SOSA Vaayu ₹12,499, ₹12,999 hotel-inspired · waterless refill oils from ₹1,049 for 100 g, from ₹1,849 for 300 g

See SOSA PawanSee SOSA Vaayu
Where I would not spend your client's money. Not on a point behind joinery or a sofa back — a ₹6,999 device at a blocked outlet is one the housekeeper unplugs within a month, and you have bought a socket, not a specification. Not on wiring that point into a lighting scene or a master switch: it reads as neat coordination on the drawing and ends as a schedule the client paid for and the housekeeper turns off at night; you will simply be told the machine does not work. And not on a plug-in device at all in a room where no point can honestly be added — if the answer is a surface conduit across finished stone the client will look at every day, take the 130 ml reed bottle at ₹1,499 to ₹1,599 instead, with a 300 ml refill at ₹2,399, and keep the electrical drawing out of it.

Questions, answered

At what height should the socket for a fragrance diffuser be on the electrical drawing?
90 cm to 120 cm above finished floor — about 2 ft 11 in to 3 ft 11 in, a band topping out at the switch-plate datum rather than sitting at the 300 mm socket datum. Dimension it: the 600 to 900 mm between those heights decides whether the device releases where a seated person breathes or under the furniture, and it is the number most often left off the drawing.
Does a plug-in fragrance diffuser need a dedicated circuit?
No. Both SOSA Pawan and SOSA Vaayu plug into an ordinary 5-amp point, and the load is small enough that the room's existing circuit is sufficient — no separate way, no isolator, nothing to coordinate. What they need is the right point in the right place; the electrical figures are on the product page.
Should the diffuser point be switched or unswitched?
Switched, with a plate switch beside it, so the client can turn the device off without reaching behind a console — but off scene control: no lighting scene, no master off, no room-off relay. The device holds its hours in the app, so a circuit dead every night is a schedule that never runs.
How far should a diffuser be from a return-air grille or an air-conditioning vent?
As a drawing rule: about 1.5 m in plan from a return-air grille, about 2 m from a ceiling supply diffuser and out of its throw, and about 1.2 m from the centre of a 1,200 mm sweep fan — twice the blade-tip radius. A return behaves roughly as a sink, its pull falling away with about the square of the distance, so three face widths from a 500 mm grille leaves near a ninth of the face velocity.
What do I do if there is no socket where the diffuser needs to go?
Three honest options. A surface conduit and plate, shown to the client and accepted before it is cut, because on finished stone it is permanent and visible. A floor box, if the floor is still open. Or no device: a 130 ml reed bottle at ₹1,499 to ₹1,599, refilled from a 300 ml bottle at ₹2,399, needs no point. I would not accept an extension lead across a finished room.
What exactly should I write in the mark-up to the electrical consultant?
One line per volume, in the same revision as the FF&E entry: point reference and room; one 5-amp point at 900 mm to 1,200 mm above finished floor, dimensioned; switched at an adjacent plate; excluded from all scene and master-off control; no dedicated circuit; clearances noted from fan, return grille, supply diffuser and any habitually open opening. Then check it appears on the next issue.

If you would rather we checked it

Send the electrical layout

Send it with the reflected ceiling plan — fans, grilles and supply diffusers marked — or just the schedule line if that is all there is. We will mark the point, its height above finished floor and its clearances, say whether the room wants SOSA Pawan or SOSA Vaayu, and tell you where the honest answer is a ₹1,499 bottle and no electrical work. Trade terms on request. A portion of every SOSA order supports girl-child education through Nanhi Kali.

Write to SOSA on WhatsApp

A portion of every SOSA order supports a girl’s education through Nanhi Kali.
SOSA Home & Body, Pune · written by Sonal Sahani, founder and perfumer, trained at ISIPCA Versailles · The Founder Diaries

Prices and specifications were taken from the SOSA product pages at publication and may change; please confirm on the product page. Volume figures given are illustrative calculations. Socket heights, clearances and switching notes here are drawing-stage guidance for a designer to coordinate, not an electrical design; circuit arrangement, protection and compliance remain the electrical consultant's. Figures attributed to general ventilation design guidance are conventions, not SOSA measurements. Coverage is published for suitable connected spaces and depends on ceiling height, ventilation and layout. Nothing here is a health or air-purification claim.

Zurück zum Blog